AGOS is designed for:
• a doser comprising an odorant purification unit, a pump and feed sensor;
• electronic control unit;
• odorant storage working block (for some version, see table);
• level sensor (for some version, see table);
• verification tank ITsFR.494529.001 used for on-line control of odorization precision (supplied individually based on data sheet).
A single injected odorant dose volume, ml | 0,31–0,6 |
Gas flow rate range at GDS, m3/h | 200–200 000 |
Operation temperature range, °С | -40 ... +50 |
Operational gas pressure in a pipeline, MPа | 0,2–1,2 |
Operation mode | Continuous, 24 hours |
Consumed power, W, at least | 15 |
Mean time between failures, h | ≥ 80000 |
Service period, years | > 10 |
Warranty period, years | 1,5 |
• computer-flowmeter Superflo-2;
• electronic volume adjuster ЕК-260;
• control point HSTMT (hardware and software telemechanic tools) (DAKZh.424332.002-39).
AGOS has explosion-proof design:
• electronic control unit [Exic] IIА;
• doser 2ExdIIAT6, 2ExicIIAT6;
• level sensor 2ExicIIAT6.
The system can generate the following signals: “Alarm” (general signal), “connection lost”, “no feed”, “The level is below the preset one”, “back up power supply” (while witching to backup power supply). In case of the supply voltage failure, the system’s equipment is fed by a backup power supply without loss of function. When a dozer is operated manually the pulses frequency for the odorant supply is set using a keyboard of indicating device’s module. If a signal entering from a computer – gas flowmeter is lost, the system carries out odorization at the previous gas flow rate. Alarm messages are accompanied by audible alarms. If the system undergoes maintenance it is possible to carry out odorization using a dropper.
Doser | 670x540x220 |
Electronic control unit (ECU) | 281x255x234 |
Level sensor | 185x76x300 |
Odorant storage tank without cover (cap) | 2450x610x2750 |
Scope of delivery:
• AGOS (designed in compliance with the above table),
Designation |
AGOS | |||
Electronic control unit (ECU) | Doser |
Level sensor |
Odorant storage tank | |
ITsFR.423314.001 | ITsFR.421413.003 (network: ~220 V or = 24 V) | ITsFR.063831.001 (200 … 50 000 m3/h) | Not available | Not available |
ITsFR.423314.001-01 | ITsFR.421413.003-01 (network: ~220 V) | ITsFR.063831.001 (200 … 50 000 m3/h) | Not available | Not available |
ITsFR.423314.001-02 | ITsFR.421413.003-02 (network: = 24 V) | ITsFR.063831.001 (200 … 50 000 m3/h) | Not available | Not available |
ITsFR.423314.001-03 |
ITsFR.421413.003 |
ITsFR.063831.001 (200 … 50 000 m3/h) | ITsFR.406411.002 | Not available |
ITsFR.423314.001-04 | ITsFR.421413.003-01 | ITsFR.063831.001 (200 … 50 000 m3/h) | ITsFR.406411.002 | Not available |
ITsFR.423314.001-05 | ITsFR.421413.003-02 | ITsFR.063831.001 (200 … 50 000 m3/h) | ITsFR.406411.002 | Not available |
ITsFR.423314.001-06 | ITsFR.421413.003 | ITsFR.063831.001-01 (1000 ... 100 000 m3/h) | Not available | Not available |
ITsFR.423314.001-07 | ITsFR.421413.003-01 | ITsFR.063831.001-01 (1000 ... 100 000 m3/h) | Not available | Not available |
ITsFR.423314.001-08 | ITsFR.421413.003-02 | ITsFR.063831.001-01 (1000 ... 100 000 m3/h) | Not available | Not available |
ITsFR.423314.001-09 | ITsFR.421413.003 | ITsFR.063831.001-01 (1000 ... 100 000 m3/h) | ITsFR.406411.002 | Not available |
ITsFR.423314.001-10 | ITsFR.421413.003-01 | ITsFR.063831.001-01 (1000 ... 100 000 m3/h) | ITsFR.406411.002 | Not available |
ITsFR.423314.001-11 | ITsFR.421413.003-02 | ITsFR.063831.001-01 (1000 ... 100 000 m3/h) | ITsFR.406411.002 | Not available |
ITsFR.423314.001-12* | ITsFR.421413.003-03 | ITsFR.063831.001-01 (1000 ... 100 000 m3/h) | ITsFR.406411.002 | Not available |
ITsFR.423314.001-13 | ITsFR.421413.003 | ITsFR.063831.001 | ITsFR.406411.002 | ITsFR. 306289.001 |
ITsFR.423314.001-14 | ITsFR.421413.003 | ITsFR.063831.001-01 (1000 ... 100 000 m3/h) | ITsFR.406411.002 | ITsFR. 306289.001 |
________________ *AGOS ITsFR.423314.001-12 has two dosers ITsFR.063831.001-01 (1000-100 000 m3/h), providing total gas output up to 200 000 m3/h. |